说明:双击或选中下面任意单词,将显示该词的音标、读音、翻译等;选中中文或多个词,将显示翻译。
您的位置:首页 -> 词典 -> 校准部件
1)  calibrator unit
校准部件
2)  ammeter calibrator group
安部计校准器组件
3)  partial calibration
局部校准
1.
A partial calibration scheme of active phased antenna arrays;
固态有源相控阵的局部校准方法研究
4)  external calibration
外部校准
1.
External calibration is an effective way to calibrate absolutely the synthetic aperture radar(SAR) system,but the external calibration method used for conventional SAR system cannot be implemented for low frequency ultra wideband(UWB) SAR system.
外部校准是实现合成孔径雷达(SAR)系统绝对定标的有效途径。
2.
And then the methods of time-variable gravity gradient corrections,outlier detection and external calibration are discussed.
讨论了重力梯度测量数据的预处理方案、时变重力场信号改正、粗差探测和外部校准方法,为进一步开展GOCE卫星重力梯度测量数据的预处理研究提供参考和具体建议。
5)  internal calibration
内部校准
6)  calibration condition
校准条件
1.
This paper analyses influence to testing results by the difference testing windows and the calibration condition in testing shielding efficiency of the plan shielding material , at the same time, how to avoid the influence is pointed out .
文章分析了在平面屏蔽材料的屏蔽效能测试中,测量窗口和校准条件的不同对测量结果的影响,并通过对实际测试数据的分析,提出了避免这种影响的措施。
补充资料:传感器如何进行无源校准及两点特别说明
a)首先读出变送器内部设置的4mA压力值和20mA压力值,看是否与实际的4mA压力值和20mA压力值相一致,若一致,则直接更改4mA压力值和20mA压力值到量程迁移后的压力值即可。

b)如果变送器内部设置的4mA压力值和20mA压力值,与实际的4mA压力值和20mA压力值不一致,可先把实际的4mA压力值和20mA压力值折算到变送器内部设置的4mA压力值和20mA压力值,再折算量程迁移后的压力值,将折算值更改到4mA压力值和20mA压力值便可。例如:假设一台变送器量程为-10bar-50bar,想将量程迁移到10bar-40bar,读出变送器内部设置的4mA 压力值和20mA压力假设为0-10Kpa,进行如下折算:-10bar 和0相对应,50bar和10Kpa相对应,通过计算,可以计算出折算方程为:P折=P实/6+10/6('P折'为折算后的压力值,'P实'为实际压力值),由此方程可计算出折算后4mA压力值应为:10/6+10/6=3.333KPa,折算后20mA的压力值应为:40/6+10/6=8.333KPa, 于是可以通过组态软件将变送器内部的4mA压力值设置为3.333,将20mA压力值设置为8.333便可。

特别说明:

1)量程迁移只能在原量程范围内迁移,若迁移超出原量程范围,则变送器的线性度变会变差。

2)进行无源校准时,量程迁移不可过大,迁移比最好不要大于3:1,过大会造成变送器输出不稳定,而且分辨率较低。大迁移比量程迁移在要先进行增益设置,再进行输入压力校准。
说明:补充资料仅用于学习参考,请勿用于其它任何用途。